- 102 -
8-2
Conflict & Interference Error
Setting function code
Error code
Description
No.
Name
Setting
1002
1st speed frequency setting
2-20
26-28
Exxxx
Cannot set analog input repeatedly
25
E1001
When 1st speed frequency is pulse train input, the required PG
sensor control mode cannot be used
1003
V/f pattern
2, 3
E2007
Automatic torque boost and square ratio lowing mode cannot
be used together
1007
Upper frequency limit
All
E1008
Upper frequency limit cannot be smaller than lower frequency
limit
E1001
Exceed the possible upper frequency limit
1008
Lower frequency limit
All
E1007/E1316
/E1317
Lower frequency limit cannot be larger than upper frequency
limit
1010
Acceleration / deceleration curve
2, 3
E2007
Automatic torque boost and S acceleration / deceleration
degression cannot be used together
1101
Operation command selection
1, 3
E1001
During position control (F1001=6), only terminal board
command (F1101=2) can be used
1301
1st jump bottom frequency
All
E1302
No larger than the value of 1st jump top frequency
1302
1st jump top frequency
All
E1301
No smaller than the value of 1st jump bottom frequency
1303
2nd jump bottom frequency
All
E1304
No larger than the value of 2nd jump top frequency
1304
2nd jump top frequency
All
E1303
No smaller than the value of 2nd jump bottom frequency
1305
3rd jump bottom frequency
All
E1306
No larger than the value of 3rd jump top frequency
1306
3rd jump top frequency
All
E1305
No smaller than the value of 3rd jump bottom frequency
1316
2nd upper frequency limit
All
E1008
Upper frequency limit cannot be smaller than lower frequency
E1001
Exceed the possible upper frequency limit/motor parameter
sheet error
1317
3rd upper frequency limit
All
E1008
Upper frequency limit cannot be smaller than lower frequency
E1001
Exceed the possible upper frequency limit/motor parameter
sheet error
1411
Analog input switching for set
frequency gain
All
Exxxx
Cannot set analog input repeatedly
1901
Energy-saving mode selection
1
E1001
Only V/f control can use simple energy-saving mode
E2007
Automatic torque boost and simple energy-saving mode cannot
be used together
E3201
PID control action and simple energy-saving mode cannot be
used together
2
E1001
Only V/f control speed control can use simple energy-saving
mode
E2007
Automatic torque boost and auto energy-saving mode cannot
be used together
2002
V•f separation command voltage
0
Exxxx
Cannot set analog input repeatedly
2007
Auto torque boost selection
Beyond
0
E1003
Automatic torque boost, cannot be used unless V/f mode is
linear
E1010
Automatic torque boost, cannot be used unless acceleration /
deceleration curve is linear
E1901
Automatic torque boost and energy-saving mode cannot be
used together
2201
Scheduled operation selection
1,2
E1001
In current control mode, scheduled or disturbed operation
cannot be used
All
Exxxx
Cannot set analog input repeatedly
2236
Disturb modulation analog input
switching
All
Exxxx
Cannot set analog input repeatedly
3001
PID1 command value input
switching
All
Exxxx
Cannot set analog input repeatedly
3002
PID1 feedback input switching
All
Exxxx
Cannot set analog input repeatedly
3101
PID2 command value input
switching
All
Exxxx
Cannot set analog input repeatedly
3102
PID2 feedback input switching
All
Exxxx
Cannot set analog input repeatedly