- 28 -
4-4
Composition of Main Circuit Terminals
400V systems
Model
External brake resistor (recommended)
External brake resistor (limit value)
Resistance
Capacity *1
Resistance
Capacity *1
SVC06-0007-
4
700Ω or more
100W
380Ω or more
150W
SVC06-0015-
4
320Ω or more
200W
190Ω or more
300W
SVC06-0022-
4
160Ω or more
400W
130Ω or more
500W
SVC06-0040-
4
120Ω or more
600W
80Ω or more
800W
SVC06-0055-
4
80Ω or more
800W
52Ω or more
1100W
SVC06-0075-
4
60Ω or more
1000W
38Ω or more
1500W
SVC06-0110-
4
40Ω or more
1500W
32Ω or more
1800W
SVC06-0150-
4
40Ω or more
1500W
32Ω or more
1800W
*1 In this example, the maximum
duty cycle
of the brake resistor is assumed to be 10% ED.
As shown in the example, to protect the brake resistor, F1115 (Duty cycle of brake resistor) shall be set at 10% ED
or less. When % ED needs to be set above 10 %, brake resistor capacity should be increased proportionally.
Example) When setting 20 % ED, the capacity should be doubled.