~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 34 -
d.
F_001
= 3
Start signal is generated by keypad, FWD and REV terminals are
useless, and the running is in the positive direction.
Note :
that for F_001=0, 2, if FWD-COM and REV-COM are open
simultaneously, the frequency display in the monitor mode will
display flashed ' ------ ', and if FWD-COM and REV-COM are
closed simultaneously, the frequency display in the monitor
mode will display flashed '
'
C.
F_002
: Select source of speed setting
a.
F_002=0
Indicate the frequency is set by terminals (select Vin, Iin analog
input by F_123)
(1) Vin-GND: range of input is 0~10V
Note: The gain and bias of analog signals refer the setting in
F_040 and F_041.
(2) Iin-GND: switch the DIP switch DSW1 on the control board.
“ I ” side: inputting current reference range 4~20mA or
0~20mA(select by F_126)
“V” side: inputting voltage reference range 2~10V or
0~10V(select by F_126)
Note : The gain and bias of analog signals refer the setting in
F_127 and F_128.
b.
F_002
= 1
Indicate the speed is set by keypad.
(1) For KP-201C, main speed and the multiple level speeds can
be set, besides, the frequency can be set in the monitor mode.
(2) For KP-202C, using setting potentiometer knob on the panel
to set speed
c.
F_002
= 2
RPM set by keypad.
d.
F_002
= 3
MPM set by keypad.
e.
F_002
= 4
Indicate the frequency is set by UP/DOWN terminals
By multi-function input terminals set UP command / DOWN
command / UP/DOWN frequency command clear/enter
functions.
Note : When F_002=1~3, in the monitor mode to change the frequency
command, push the
and
key one time, the frequency
command will blink but the value doesn’t changed, push the key
again then can start to change the value.