~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 65 -
(18) Speed tracking
A.
F_088
:
Current for speed tracking
The range of level of current for speed tracking is
0~200% of the rated current of inverter.
B.
F_089
:
Time interval for speed tracking
The range of time interval for speed tracking is 0.5~5.0
seconds.
C.
F_090
: V/F pattern of speed tracking
The range of this function is 0~100 % of voltage of the
V/F pattern
a. The function of speed tracking is primarily used to resume
speed after instantaneous power interruption, fault conditions
and search speed commanded by external input terminals.
b. Refer to the speed search programmed by multiple
function
input terminals.
(19) Settings of creep
A.
F_096
:
Creeping frequency setting
The range of creeping frequency setting is 0.0~400.0 Hz.
B.
F_097
:
Time duration of creep
The range of time duration of creep is 0.0~25.5 seconds.
The function of creep is to avoid the higher slip in
acceleration.
Output frequency
Time
Creeping frequency
setting (F_096)
Time during of
creep (F_097)