~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 63 -
(16) Resumption after instantaneous power interruption
A.
F_078
: Selection of resumption
0 : Inverter can not be restarted after instantaneous power
interruption.
1 : Inverter will be restarted after instantaneous power
interruption. (Refer to detection of restart after
instantaneous power interruption)
2 : Shutdown
3 : Inverter will decelerate at the moment then restart after
the instantaneous power interruption.
B.
F_079
: Level of power source for shutdown
The ranges of the level of power source for shutdown are 150.0
~192.0 V for 200V class and 300.0~384.0 V for 400V class.
C.
F_ 103
: Decrease frequency of shutdown with range
0.0 ~20.0Hz.
D.
F_ 104
: Deceleration time 1 of shutdown with range
0.0 ~ 3200.0 seconds.
E.
F_ 105
: Deceleration time 2 of shutdown with range
0.0 ~ 3200.0 seconds.
F.
F_ 106
: Switch frequency of shutdown with range
0.0 ~ 400.0Hz.
Note : This shutdown function is proper to inertial load.
Shutdown
Power source
Deceleration time 2 (F_105)
Output
frequency
Switch frequency
(F_106)
Time
Deceleration time 1 (F_104)
Decrease frequency of
deceleration time (F_103)