~INSTALLATIONS AND CONFIRMATIONS~
- 12 -
c.
Terminals of control circuit
Terminals
Symbols
Name Descriptions
FWD Forward
operation
FWD-COM is short-circuit for
forward operation
REV Reverse
operation
REV-COM is short-circuit for
reverse operation
X1 Multiple function
input terminal 1
Function is determined by
F_052
X2 Multiple function
input terminal 2
Function is determined by
F_053
X3 Multiple function
input terminal 3
Function is determined by
F_054
X4 Multiple function
input terminal 4
Function is determined by
F_055
X5 Multiple function
input terminal 5
Function is determined by
F_056
X6 Multiple function
input terminal 6
Function is determined by
F_057
COM Common of input
terminals
Common of input terminal
signals
Vin
Voltage type of
frequency
command input
Input range 0 ~ 10V
Input
terminals
Iin
Current type of
frequency
command input
DSW1-> I side
(current input)
DSW1-> V side
(voltage input)
Input range
DC4~20 mA (2~10V)
/0~20mA(0~10V)
The range determined by F_126
+12V
Reference
voltage of control
signals
12V reference voltage with
maximum current 20mA
Control circuit
Power
Source
GND Ground of
control signals
Ground of control signals