LIST OF FUNCTION CODE SETTING~
- 32 -
Function
Name
Descriptions
Range of
setting
Resolu-
tion
Factory
setting
No. page
reference
for detail
F_129
Selection of
AM+ analog
output
signal
0:Analog signal indicates output frequency
1:Analog signal indicates frequency command
2:Analog signal indicates output current
3:Analog signal indicates Vin frequency command
4:Analog signal indicates Iin frequency command
0~4
—
2
46
F_130 AM+ analog
output gain
Gain=max output frequency/output frequency.
Or Gain=rated current of inverter/output current
0.00~2.00
0.01 1.00 46
F_131
Setting of
output terminals
Ta2 and Tc2
Refer the setting of multiple function outputs
-11
∼
11
(Re.9)
—
1
54
F_132
Frequency of
DC braking in
stop
Start frequency of DC braking in stop
0.1~60.0 0.1HZ 0.5
62
F_133 Current
limit level
Monitor the current limit level setting
—
—
—
53
0
:
Useless
CLF
:
Clear fault records
dEF60 : Resume the factory setting of 60 Hz
dEF50 : Resume the factory setting of 50 Hz
SAv
:
Store setting
rES
:
Resume setting
rd-EE
:
Digital keypad
(
KP-201C
)←
inverter
parameters
F_134
Selections of
resumption of
factory setting
Wr-EE
:
Digital keypad
(
KP-201C
)→
inverter
parameters
—
—
0
36
Remark:
(1) Factory settings for 50 Hz
(2) Factory settings for 60 Hz
(3) Specifications of 200V
class.
(4) Specifications of 400V
class .
(5) 0.5~5 HP: 5 sec
7.5~30 HP:15 sec
above 40 HP: 30 sec
(6) Display 'OLO '
(7) The dynamic braking unit is installed.
(8) The setting is zero to denote that there is no
display.
(9) + : represents contact a (normally open)
- : represents contact b (normally close)
UP/DOWN control wiring must be less than
20M.
(10) Above 125HP for RM5P series, the factory
setting of F_081=3
The color as
means which can be set during operation