OPERATIONS OF KEYPADS ~
- 25 -
B. Descriptions of DIP functions
No.
Switch
DIP Functions
Descriptions
Remark
1
ON
1 2 3 4
Carry
frequency
ON: Carry frequency is 2.5KHz
OFF: use KP-201C set the carry
Frequency(Factory setting)
Refer
to P.70
2
ON
1 2 3 4
Selections of
base
frequency
ON: Base frequency at 50.00Hz
OFF: Base frequency at 60.00Hz
Refer
to P.70
3
ON
1 2 3 4
Selections of
speed setting
ON: frequency set by terminal
OFF: frequency set by KP-201C
primary speed or KP-202C
setting (Factory setting)
Refer
to P.70
4
ON
1 2 3 4
Selections of
start
command
ON: start with the FWD/REV
terminal
OFF: use the KP-202C start
(Factory setting)
Refer
to P.70
C. Descriptions of ADJ functions
ADJ
Functions Range Factory
setting
Remark
Boost voltage
0.1~127.5V
8.0V(200V class)
12.0V(400V class)
Refer
to P.71
Primary
acceleration time 0.0~165.0 sec
0.5~5HP : 5.0 sec
7.5~30HP:15.0 sec
above 40HP:30.0 sec
Refer
to P.71
Primary
deceleration time 0.0~165.0 sec
0.5~5HP : 5.0 sec
7.5~30HP:15.0 sec
above 40HP:30.0 sec
Refer
to P.71
Speed level 1
0.0~120.0Hz
10.0Hz
Refer
to P.71
Max. output
frequency
0.0~120.0Hz
60.0Hz
Refer
to P.71
Secondary
Acc/Dec time
0.0~165.0 sec
0.5~5HP : 5.0 sec
7.5~30HP:15.0 sec
above 40HP:30 sec
Refer
to P.71
FREQ
Primary
setting
0.0~120.0Hz
----
Refer