~INSTALLATIONS AND CONFIRMATIONS~
- 13 -
Terminals
Symbols
Name
Descriptions
FM+
AM+ Analog output
1.Use a 10V full scale meter
(impedance: 10KΩ or higher)
2.The maximum output current is
1mA.
M- Ground of
analog output
signals
Ground of analog output signals
Ta1
The function of contact a (normal
open) is determined by F_060.
(The capacity of contact is
250VAC, 0.5A and Cos
φ
=0.3)
Tb1
The function of contact b (normal
close) is determined by F_060.
(The capacity of contact is
250VAC, 0.5A and Cos
φ
=0.3)
Tc1
Common terminals of Ta1 and
Tb1
Ta2
The function of contact a (normal
open) is determined by F_131.
(The capacity of contact is
250VAC, 0.5A and Cos
φ
=0.3)
Control circuit
Output
terminals
Tc2
Multiple
function output
terminals
(Relay outputs)
Common terminals of Ta2
Y1
Y2
Function is determined by
F_058/F_059.
(The maximum capacity is
DC48V,50mA)
CME
Multiple
function output
terminals
(Open-collector
outputs)
Common terminals of Y1 and Y2
GND