C. The notes and specifications of wiring
a. The leakage current between ground and the wires that are
connected between inverter and motor, is not the same for
different rated power. The setting of carry frequency (F_81)
relate to the rated power and wire distance. Referred to the
figure shown below.
Distance
Rated
Power
10m 25m 50m 100m
Above
100m
1/2~5HP 12.5KHz
or less
10KHz
or less
7.5KHz
or less 5KHz or less 2.5KHz
7.5~10HP 10KHz
or less
7.5KHz
or less
5KHz
or less
2.5KHz 2.5KHz
15~30HP 7.5KHz
or less
5KHz
or less 2.5KHz
2.5KHz 2.5KHz
40~75HP
5KHz
or less 2.5KHz 2.5KHz
2.5KHz 2.5KHz
100~420HP 2.5KHz 2.5KHz 2.5KHz
2.5KHz 2.5KHz
P.S. The carry frequency is determined by F_081.
b.
If the inverter is used where the altitude is greater than 1000 m,
the relationship between current and altitude should be
mentioned and referred to the figure shown below.
60%
70%
80%
100%
90%
0
3000
Altitudes(m)
4000
2000
1000
Percentage
of the rated
current of
inverter