~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 43 -
Output
frequency
Analog
command
Analog
command
72.0Hz
60.0Hz
48.0Hz
0Hz
0Hz
0V(4mA)
0V(4mA)
8.3V(17.3mA)
10V(20mA)
10V(20mA)
Analog freq. command bias=0.00
Max. output freq. = 60.0Hz
Frequency command gain=1.20
Max. output freq. = 60.0Hz
Frequency command gain=0.80
Output
frequency
×
analog command input
(5) Analog input commands
A.
F_040
: Vin frequency command gain with range 0.00~2.00.
F_127
: Iin frequency command gain with range 0.00~2.00.
a. Analog input terminals are Vin range 0~10V; Iin range
4~20mA(2~10V) or 0~20mA(0~10V).
b. The maximum frequency setting = max. output freq. (F_031)
analog command gain ( F_040/F_127)
B.
F_041
: Vin frequency command bias with range -1.00~1.00.
F_128
: Iin frequency command bias with range -1.00~1.00.
a. Bias frequency = max. output freq. (F_031)
×
analog
command bias ( F_041/F_128).
b. Frequency setting =
(Max. frequency setting – bias frequency)
10V(20mA)
+ bias frequency
60.0Hz
60.0Hz
3.0Hz
-3.0Hz
0V(4mA)
0V(4mA)
0.5V(4.8mA)
10V(20mA)
10V(20mA)
Analog
command
Analog
command
Analog freq.command gain=1.00
Max. output freq. = 60.0Hz
Frequency command bias=0.05
Max. output freq. = 60.0Hz
Frequency command bias= -0.05
Output
frequency
Output