~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 53 -
FWD RUN
REV RUN
RUN
STOP
FWD/REV
F_001=0
F_056=0
FWD
REV
X5
COM
FWD
REV
X6
COM
'OFF ':FWD
'ON ':REV
F_001=1
F_057=0
STOP
(3)
F_054
: Input terminal X3 setting
F_133
: current limit level
F_054=0 current limit enable
Use KP-201C digital keypad
X3 and COM close
→
F_124 or F_125=2
→
the current limit
enable
→
monitor F_133(range 1~150% inverter rated
current)
X3 and COM open
→
monitor F_133
→
the value is the same
as the F_071.
Use KP-202C analog keypad
X3 and COM close
→
current limit enable
→
the setting
potentiometer of KP-202C function is current limit(range
1~150% monitor the RSW 7)
EX:F_054=0
,
X3 and COM close
,
F_124=2, F_125=1,
the Vin input 0~10V
→
1~150% inverter rated current.
(4)
F_055
: Input terminal X4 setting
0: primary and secondary speed select
F_122
: Selection of secondary speed
0: indicate that the frequency is set by terminals
1: indicate that the frequency is set by keypad
2: indicate that the frequency is set by UP/DOWN
terminals
(5)
F_056
: Input terminal X5 setting
(6)
F_057
: Input terminal X6 setting
0: STOP command with 3line sustaining circuit in
which X5 is contact a, X6 is contact b, and other
terminals are useless.