Caution:
The DXi3500/DXi5500 system is designed to be installed
in a rack enclosure. Ensure that the operating temperature
inside the rack enclosure does not exceed the maximum
rated ambient temperature. Do not restrict air flow to the
DXi3500/DXi5500 components.
Appendix A DXi3500/DXi5500 System Specifications
Environmental Specifications
Quantum DXi3500 and DXi5500 User’s Guide
166
Climatic Environment
Temperature
Operating
50° F to 95° F
(10° C to 35° C)*
Shipping and
storage
-4° F to 140° F
(-20° C to 60° C)
Relative humidity
Operating
20% to 80%, non-condensing
Shipping and
storage
15% to 95%, non-condensing
Altitude
Operating
0 to 10,000 ft.
(0 to 3,048 m)
Shipping and
storage
0 to 39,370 ft.
(0 to 12,000 m)
Heat
Operating
1,706 Btu/hour (DXi3500)
2,560 Btu/hour (DXi5500)
Acoustical Noise
Sound power
level
Operating
8.10 Bel
Idle
7.83 Bel
Sound pressure @
bystander
Operating
63db
* 35°C (95°F) is the maximum temperature for the DXi3500/DXi5500 at sea
level. For every 1000 feet (305 meters) of altitude, the maximum temperature is
reduced by 1° (example: the maximum temperature for a DXi3500/DXi5500 at
1000 feet (305 meters) is 34°C (93°F).