Buffer storage tank
Domestic water storage tank
4
Buffer storage tank, heat generation shutoff valve
04
Primary pump
5
Buffer storage tank, solar connection
05
Charging pump, solar connection
Heat gen shutoff valve
13
Diverter valve
14
Diverting valve, solar connection
16
Primary controller, without heat exchanger
17
Primary controller, 1 heat exchanger
19
Intermediate circuit, without heat exchanger
20
Intermediate circuit, 1 heat exchanger
22
Primary pump/intermediate circuit, without heat ex
changer
23
Charging pump/intermediate circuit, 1 heat exchanger
25
Diverting valve, intermediate circuit, without heat ex
changer
26
Diverting valve, intermediate circuit, 1 heat exchanger
28
Primary controller/intermediate circuit, without heat
exchanger
29
Primary controller/intermediate circuit, 1 heat ex
changer
Tab.25 Check no. heating circuit (prog.-no. 6217)
Heating circuit 3
Heating circuit 2
Heating circuit 1
0
No heating circuit
00 No heating circuit
00 No heating circuit
1
DHW circulation via boiler circuit
pump
01 DHW circulation via boiler circuit
pump
01 DHW circulation via boiler circuit
pump
2
Heating circuit pump
02 Heating circuit pump
02 Heating circuit pump
3
Heating circuit pump, mixer
03 Heating circuit pump, mixer
03 Heating circuit pump, mixer
Software version (6220)
Display of the actual software version.
9.2.18 LPB system
Device address (6600) andSegment address (6601)
The two-part LPB address of the controller consists of the 2-digit segment
number and the 2-digit device number.
Bus power supply function (6604)
Off: The controller does not provide the bus power supply.
Automatically: The bus power supply is switched on and off by the con
troller in accordance with the power demand of the bus system.
Bus power supply state (6605)
Off: The bus system power supply by the controller is currently inactive.
On: The bus system power supply by the controller is currently active.
Display system messages (6610)
This setting allows system messages which are transmitted via LPB to be
suppressed on connected operating elements.
Alarm delay (6612)
The transmission of the alarm to the BM module can be delayed in the ba
sic device by an adjustable time. This allows the prevention of unnecessa
ry messages to a service location caused by malfunctions which only oc
cur briefly (e.g. temperature monitor queried, communication errors). How
9 Settings
7658013 - 02 - 15092016
Paramount four 30 – 115 kW