
DHW
Prog. no.
Level Standard value
Release
24h/day | Time setting central heating | Time hot water
1620
Eu
Time hot water
Charging priority
Absolute | Shifting | None | MC shifting, PC absolute
1630
E
MC shifting, PC
absolute
Legionella function
Off | Periodically | Fixed weekday
1640
E
Fixed weekday
Legionella funct periodically
1641
E
7
Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday | Saturday | Sunday
1642
E
Sunday
Legionella funct time
1644
E
- - -
Legionella funct setpoint
1645
E
65 °C
Legionella funct duration
1646
E
- - - min
Legionella funct circ pump
Off | On
1647
E
On
Circulating pump release
Time setting 3/CHP | Hot water release | Time hot water | Time auxiliary
1660
C
Hot water release
Circulating pump cycling
Off | On
1661
C
On
Circulation setpoint
1663
E
55 °C
Optg mode changeover
None | Off | On
1680
E
Off
Consumer circuit / swimming pool circuit
Consumer
circuit 1
Prog. no.
Consumer
circuit 2
Prog. no.
Swimming
pool circuit
Prog. no.
Level Standard value
Flow temp setp cons request
1859
1909
1959
C
70 °C
Hot water charging priority
No | Yes
1874
1924
1974
E
Yes
Excess heat draw
Off | On
1875
1925
1975
E
On
With buffer
No | Yes
1878
1928
1978
E
Yes
With prim contr/system pump
No | Yes
1880
1930
1980
E
Yes
Swimming pool
Prog. no.
Level Standard value
Setpoint solar heating
2055
Eu
26°C
Setpoint source heating
2056
Eu
22°C
Charging priority solar
Priority 1 | Priority 2 | Priority 3
2065
E
Priority 3
Swimming pool temp max
2070
E
32 °C
With solar integration
No | Yes
2080
E
Yes
Primary control/feed pump
Prog. no.
Level Standard value
Flow temp setpoint min
2110
E
8 °C
Flow temp setpoint max
2111
E
80 °C
Syst pump on heat gen lock
Off | On
2121
E
Off
Mixing valve boost
2130
E
0 °C
Actuator running time
2134
E
140 s
9 Settings
7658013 - 02 - 15092016
Paramount four 30 – 115 kW
61