Time program heating circuit 4 / DHW
Prog. no.
Level Standard value
3rd Time ON
565
Eu
--:-- (h/min)
3rd Time OFF
566
Eu
--:-- (h/min)
Copy?
575
Eu
No
Default values
No | Yes
576
Eu
No
Time program heating circuit 5
Prog. no.
Level Standard value
Select Mon-Sun
Mon-Sun | Mon-Fri | Sat-Sun | Mon | Tue | Wed | Thu | Fri | Sat | Sun
600
Eu
Mon
1st Time ON
601
Eu
06:00 (h/min)
1st Time OFF
602
Eu
22:00 (h/min)
2nd Time ON
603
Eu
--:-- (h/min)
2nd Time OFF
604
Eu
--:-- (h/min)
3rd Time ON
605
Eu
--:-- (h/min)
3rd Time OFF
606
Eu
--:-- (h/min)
Copy?
615
Eu
No
Default values
No | Yes
616
Eu
No
Holidays heating circuit
1
Prog. no.
Prog. no.
3
(1)
Prog. no.
Level Standard value
Select
Period 1 | Period 2 | Period 3 | Period 4 | Period 5 |
Period 6 | Period 7 | Period 8
641
651
661
Eu
Period 1
Start
642
652
662
Eu
—.— (day.month)
End
643
653
663
Eu
—.— (day.month)
Operating level
Off | Reduced
648
658
668
Eu
Off
(1) Parameters only visible if heating circuit is installed!
Heating circuit
1
Prog. no.
2
Prog. no.
3
(1)
Prog. no.
Level Standard value
Comfort setpoint
710
1010
1310
Eu
20.0 °C
Reduced temp setpoint
712
1012
1312
Eu
18 °C
Frost protection setpoint
714
1014
1314
Eu
10.0 °C
Heating curve slope
720
1020
1320
Eu
1.24
Heating curve displacement
721
1021
1321
E
2.0 °C
Heating curve adaption
Off | On
726
1026
1326
E
Off
Summer/winter heating limit
730
1030
1330
Eu
18°C
24-hour heating limit
732
1032
1332
E
0 °C
Flow temp setpoint min
740
1040
1340
E
8 °C
Flow temp setpoint max
741
1041
1341
E
80 °C
Flow temp setpoint room stat
742
1042
1342
E
- - - °C
Swi-on ratio room stat
744
1044
1344
E
- - - %
Delay heat request
746
1046
1346
E
0 s
Room influence
750
1050
1350
C
- - - %
Room temp limitation
760
1060
1360
E
0.5 °C
Central heating boost
770
1070
1370
E
- - - °C