Boiler
Prog. no.
Level Standard value
Fan output heating max
2441
E
Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Fan output full charging max
(1)
2442
E
Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Fan output DHW max
(1)
2444
E
Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Controller delay
Off | Heating mode only | Hot water mode only | Heating and HW mode
2450
E
Heating mode only
Controller delay fan output
(1)
2452
E
Paramount four 30:
10,0 kW; Paramount
four 40: 14.0 kW
Paramount four 50:
20,0 kW; Paramount
four 60: 22,5 kW; Pa‐
ramount four 80: 34,5
kW; Paramount four
95: 36,0 kW; Para‐
mount four 115: 40.0
kW
Controller delay duration
2453
E
40 s
Switching diff on CHs
2454
E
4 °C
Switching diff off min CHs
2455
E
5 °C
Switching diff off max CHs
2456
E
10 °C
Switching diff on HW
2460
E
5 °C
Switching diff off min HW
2461
E
6 °C
Switching diff off max HW
2462
E
8 °C
Delay heat req special op
2470
E
0 s
Pressure switch shutdown
Start prevention | Lockout position
2500
E
Start prevention
Gas energy metering
Off | On
2550
C
Off
Gas energy metering correction
2551
C
1.0
(1) The kW settings are approximate values. Exact values can be determined by the gas meter for example.
9 Settings
7658013 - 02 - 15092016
Paramount four 30 – 115 kW
63