Caution
Risk of damage to the burner!
Too
high
CO
2
values can lead to unhygienic combustion (high CO
values) and damage to the burner.
Too
low
CO
2
values can lead to ignition problems.
The CO
2
value is set by adjusting the gas pressure at the gas valve. If the
Paramount four is used in areas with fluctuating natural gas composition,
the CO
2
content must be adjusted in accordance with the Wobbe index at
any given time (ask the gas supply company).
The CO
2
content to be set can be decided as follows:
CO
2
content = 8.5 - (W
oN
- W
ocurrent
) * 0,5
until Paramount four 50: CO
2
content = 8,5 - (W
oN
- W
ocurrent
) * 0,5
above Paramount four 50: CO
2
content = 8.8 - (W
oN
- W
ocurrent
) * 0.5
The air quantity set in the factory must not be changed.
For more information, see
7.4.4 Changing over from natural gas to LPG and vice versa
Danger
Danger! Danger to life by gas!
The gas type of the Paramount four may only be changed by an
approved heating specialist. The Potterton Commercial conver
sion kit for LPG (accessory) must be used. The instructions of the
conversion kit must be observed!
The CO
2
content is set by adjusting the injection nozzle pressure on the
gas valve.
The CO
2
-content must be between the values according to section
Techni
cal Data
at full load as well as low load.