5.3.3 Operation in wet rooms
In the supplied status, the Paramount four conforms in case of room air-
independent operation to international protection type IPx4D (see Fig.)
In the case of installation in wet rooms, the following conditions must be
met:
Room air-independent operation
to maintain IP rating IPx4D:
Do not operate the room device or thermostat in wet rooms.
All outgoing or incoming electrical lines must be installed through ten
sion release screw fittings and fixed.
Caution
The screw fittings have to be tightened, so that no water can enter
the inside of the housing!
1 Protection area 2
2 Protection area 3
When the Paramount four is installed in bath or shower rooms in resi
dential buildings, the protection areas and minimum clearances must be
heeded.
The Paramount four complies with IP rating IPx4D (protection area 2 or
1) and may be installed in protection area 2 (refer also to the above
notes “Operation in wet rooms”).
The Paramount four may only be installed in protection area 1 if no wa
ter jets are to be expected (e.g. massage showers).
Fig.13 Clearances in bathrooms and show
er rooms
1
1
2
2
RA-0000053