Programming
Page
D-58
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
Parameter Descriptions
I2T INHIBIT
PREF: 84.11
Default: FALSE
Range: FALSE / TRUE
This parameter allows you to enable/disable the I2T trip action. The drive continues to look for the motor load, but does not
trip if the level is higher than 100%:
FALSE : I2T trip is enabled
TRUE : I2T trip is disabled.
MOTOR I2T TRIP
PREF: 84.12
Default:
Range: FALSE / TRUE
This diagnostic reports on the state of the I2T motor trip:
FALSE :
the motor is running, the level of the motor load is lower than 100% (if the trip is active)
TRUE :
the drive has tripped, the level of motor load is higher than 100%