890SD Minimum Control Connections
Minimum Connections
Speed Reference
♦
Connect a 10k
Ω
potentiometer at terminal
X12:
X12/01 : Low (CCW)
X12/04 : Wiper
X12/08 : High (CW)
♦
Connect the shield to
earth/ground at the control
bracket.
OR
♦
External 2-wire speed
reference between:
X12/01 : negative
X12/04 : positive
♦
Connect the shield to
earth/ground at the control
bracket.
Sequencing
♦
RUN (maintained contact)
X14/03 : 24V
X15/02 : RUN
Programming Port
USB
0V
AIN3 - REMOTE SETPOINT
+10V
Speed
Potentiometer
24V
Auxiliary Supply
(optional)
24V
24V DC
0V
DIN2 - RUN
To control bracket
Programming Port
USB
AIN3 - REMOTE SETPOINT
+10V
Speed
Potentiometer
24V
DIN2 - RUN
To control bracket
24V DC
0V
24V DC
0V
0%
100%
Uni-directional
speed demand
Bi-directional
speed demand
0%
+100%
-100%
-10V