Programming
Page
D-88
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
Parameter Descriptions
PHASE SHIFT
PREF: 133.20
Default: 0.00
Range: 0.00 to 180.00°
Set a phase shift in degrees between the carrier and the sin/cos signals coming from the resolver.
Carrier :
Sin/cos signals, motor in rotation :
Carrier
8 kHz
Cos &
Sin
Phase shift ~ 45°
If unknown, use the default value.
TRIP SELECTION
PREF: 133.21
Default: 2
Range: See below
Select the trip detection based on hardware and/or software detection:
Enumerated Value : Trip Selection
0 : HARD AND SOFT
The trip is based on hardware and software detection.
1 : HARD
The trip is only based on hardware detection.
2 : SOFT
The trip is only based on software detection.