26.4 Positioning Memory
26-41
Offset
Address Name
Default Setting range and description
H29
JOG operation
setting code
H0
Sets the mode of the JOG operation.
bit
Name
Default
Description
0
-
-
-
1
Acceleration/deceler
ation pattern setting
0
0: Linear
acceleration/deceleration
1: S-shaped
acceleration/deceleration
15-2
-
-
-
H2A
JOG operation
acceleration time
K100
Sets the acceleration/deceleration time when performing the JOG
operation. At the beginning of the JOG operation, accelerates for the
specified acceleration time, decelerates for specified deceleration time
when the starting contact of the JOG operation turns off, and stops.
Setting range: 0-10,000 (ms)
Any other settings will be errors.
H2B
JOG operation
deceleration time
H2C-H2D
JOG operation
target speed
K1000
Set the target speed for performing the JOG operation. After starting
the JOG operation, accelerates to the target speed while the starting
contact of the JOG operation is on. After reaching the target speed,
operates at the target speed.
Range: 1-2,147,482,624
Any other settings will be errors. The ranges vary depending on the
unit settings as below.
pulse: 1-2,147,482,624 pps
μm: 1
-
2,147,482,624 μm/s
inch: 0.001-2,147,482.624 inch/s
degree: 0.001-2,147,482.624 rev/s
Summary of Contents for FP-XH M8N16PD
Page 1: ......
Page 23: ...1 System Structure ...
Page 39: ...2 Control Unit Specifications ...
Page 48: ...Control Unit Specifications 2 10 ...
Page 49: ...3 I O Allocation ...
Page 77: ...4 Installation ...
Page 89: ...5 Wiring of Power Supply and General purpose I O Parts ...
Page 104: ...Wiring of Power Supply and General purpose I O Parts 5 16 ...
Page 105: ...6 Wiring of Motion I O Parts ...
Page 116: ...Wiring of Motion I O Parts 6 12 ...
Page 117: ...7 Power On Off and Check Items ...
Page 124: ...Power On Off and Check Items 7 8 ...
Page 125: ...8 Steps Before Running ...
Page 142: ...Steps Before Running 8 18 ...
Page 143: ...9 Setting of Position Control Parameters ...
Page 159: ...10 Transfer to Unit and Commissioning ...
Page 181: ...11 Automatic Operation Position Control ...
Page 193: ...11 2 Interpolation Control 11 13 ...
Page 209: ...12 Automatic Operation Synchronous Control ...
Page 251: ...13 Manual Operation JOG Operation ...
Page 256: ...Manual Operation JOG Operation 13 6 ...
Page 257: ...14 Manual Operation Home Return ...
Page 264: ...Manual Operation Home Return 14 8 ...
Page 265: ...15 Pulse Input Function ...
Page 278: ...Pulse Input Function 15 14 ...
Page 279: ...16 Stop Function ...
Page 285: ...17 Auxiliary Function ...
Page 329: ...18 Instruction Reference ...
Page 357: ...19 Error Warning Annunciation Function ...
Page 386: ...Error Warning Annunciation Function 19 30 ...
Page 387: ...20 Troubleshooting ...
Page 402: ...Troubleshooting 20 16 ...
Page 403: ...21 Memory Master Memory Cassette ...
Page 418: ...Memory Master Memory Cassette 21 16 ...
Page 419: ...22 Security Functions ...
Page 430: ...Security Functions 22 12 ...
Page 431: ...23 General purpose Input High speed counter Function ...
Page 448: ...General purpose Input High speed counter Function 23 18 ...
Page 449: ...24 Other Functions ...
Page 452: ...Other Functions 24 4 ...
Page 453: ...25 Maintenance and Inspection ...
Page 457: ...26 Specifications ...
Page 552: ...Specifications 26 96 ...
Page 553: ...Record of changes Manual No Date Record of Changes WUME FPXHM8N16PD 01 Sep 2017 First Edition ...
Page 554: ......
Page 555: ......
Page 556: ......