17.5 Current Value Update
17-9
17.5 Current Value Update
The current value update function is used to set the "current value after conversion of unit
system" saved in the positioning memory to any value.
•
Set the value as the current value via the user program in the current value update
coordinates area (positioning memory area no.0/Address HC8-HD7) of the positioning
memory.
•
When the bit of the target axis of the current value update question flag area (positioning
memory area no.0/Address HC0) is set to ON, the "current value after conversion of unit
system" of the information area of each axis (positioning memory area no.1/Address H3E-
H3F) will be changed to the designated current value.
Sample program
An example of presetting any value K100000 in the positioning memory area to update the
current value after conversion of unit system of axis-1 is given below. In the first line of the
program, read the current value after conversion of unit system of axis-1 to the data registers
DT0-DT1 for monitoring.
R2
(
)
DF
R1
(
)
DF
ⓑ
F1 DMV
DT100
K100000
DT100
HC8
K2
H0
F385 PTBLW
ⓒ
F0 MV
DT102
H1
DT102
HC0
K1
H0
F385 PTBLW
R9010
ⓐ
H3E
DT0
K2
H1
F384 PTBLR
①
⑦
⑥
⑤
④
④
③
②
Code
Content specified by
program
Value specified by program
Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Axis 7
(virtual)
Axis 8
(virtual)
①
Axis no. and each
information area
H1 H101 H201 H301 H401 H501
H601
H701
②
Memory area for unit
conversion current values
H3E
③
Update value
Arbitrary value
④
Common area
H0
⑤
Current value update
coordinate area
HC8
HCA HCC HCE
HD0
HD2
HD4
HD6
⑥
Set value of current value
update request flag area
H1
H2
H4
H8
H10
H20
H40
H80
⑦
Current value update
request flag area
HC0
Summary of Contents for FP-XH M8N16PD
Page 1: ......
Page 23: ...1 System Structure ...
Page 39: ...2 Control Unit Specifications ...
Page 48: ...Control Unit Specifications 2 10 ...
Page 49: ...3 I O Allocation ...
Page 77: ...4 Installation ...
Page 89: ...5 Wiring of Power Supply and General purpose I O Parts ...
Page 104: ...Wiring of Power Supply and General purpose I O Parts 5 16 ...
Page 105: ...6 Wiring of Motion I O Parts ...
Page 116: ...Wiring of Motion I O Parts 6 12 ...
Page 117: ...7 Power On Off and Check Items ...
Page 124: ...Power On Off and Check Items 7 8 ...
Page 125: ...8 Steps Before Running ...
Page 142: ...Steps Before Running 8 18 ...
Page 143: ...9 Setting of Position Control Parameters ...
Page 159: ...10 Transfer to Unit and Commissioning ...
Page 181: ...11 Automatic Operation Position Control ...
Page 193: ...11 2 Interpolation Control 11 13 ...
Page 209: ...12 Automatic Operation Synchronous Control ...
Page 251: ...13 Manual Operation JOG Operation ...
Page 256: ...Manual Operation JOG Operation 13 6 ...
Page 257: ...14 Manual Operation Home Return ...
Page 264: ...Manual Operation Home Return 14 8 ...
Page 265: ...15 Pulse Input Function ...
Page 278: ...Pulse Input Function 15 14 ...
Page 279: ...16 Stop Function ...
Page 285: ...17 Auxiliary Function ...
Page 329: ...18 Instruction Reference ...
Page 357: ...19 Error Warning Annunciation Function ...
Page 386: ...Error Warning Annunciation Function 19 30 ...
Page 387: ...20 Troubleshooting ...
Page 402: ...Troubleshooting 20 16 ...
Page 403: ...21 Memory Master Memory Cassette ...
Page 418: ...Memory Master Memory Cassette 21 16 ...
Page 419: ...22 Security Functions ...
Page 430: ...Security Functions 22 12 ...
Page 431: ...23 General purpose Input High speed counter Function ...
Page 448: ...General purpose Input High speed counter Function 23 18 ...
Page 449: ...24 Other Functions ...
Page 452: ...Other Functions 24 4 ...
Page 453: ...25 Maintenance and Inspection ...
Page 457: ...26 Specifications ...
Page 552: ...Specifications 26 96 ...
Page 553: ...Record of changes Manual No Date Record of Changes WUME FPXHM8N16PD 01 Sep 2017 First Edition ...
Page 554: ......
Page 555: ......
Page 556: ......