Preparing for Cooling
Configuration
BTU/Hour
kj/Hour
Typical
8,654
9,129
Maximum
11,516
12,149
HC Quarter rack
Typical
8,061
8,505
Maximum
2,037
2,149
Individual EF storage server
Typical
1,426
1,504
Maximum
1,825
1,926
Individual HC storage server
Typical
1,278
1,348
The direction of airflow is front to back for the main and expansion racks.
Caution -
Do not restrict the movement of cool air from the air conditioner to the cabinet, or the
movement of hot air out of the rear of the cabinet.
Observe these additional requirements:
■
Allow a minimum clearance of 914 mm (36 inches) at the front of the rack, and 914 mm (36
inches) at the rear of the rack for ventilation. There is no airflow requirement for the left and
right sides, or the top of the rack.
■
If the rack is not completely filled with components, cover the empty sections with filler
panels.
108
Oracle SuperCluster T5-8 Owner's Guide • May 2016
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...