Operation Manual
Section 5
DETAILED SETTINGS
This section describes how to set the output range, using an example of current output
with a range with the following conversions:
−
0.5 mm to 16 mA and 0.5 mm to 8 mA.
Change the values in the example to suit the voltage output as required.
1.
Turn OFF the power supply to the Amplifier Unit.
2.
Move the current/voltage switch to current out-
put. The switch is found on the bottom of the
Amplifier Unit.
A voltage output is the default setting.
Moving to FUN and SPCL
3.
Turn ON the power supply and move the
mode switch to FUN.
4.
Use the LEFT and RIGHT Keys to display
SPCL on the main display.
Moving to FOCUS
5.
Press the UP or DOWN Key.
The sub-display will flash.
6.
Use the Up and DOWN Keys to display SET
or ALL.
7.
Press the ENT Key.
Measured
value (mm)
Output current (mA)
Measured
value (mm)
Output current (mA)
20
−
0.5
4
0.5
16
8
−
0.5
0.5
Voltage output
Current output
(mm)
POWER
ENABLE
ZERO
SUB
Summary of Contents for ZX-T -
Page 1: ...OPERATION MANUAL Smart Sensors ZX T Series Cat No E346 E1 04 ...
Page 9: ...6 Preface Contents ZX T Operation Manual PREFACE ...
Page 15: ...12 Preface How to Use This Manual ZX T Operation Manual PREFACE ...
Page 16: ...Section 1 FEATURES 13 ZX T Operation Manual Section 1 FEATURES ZX T Features 14 ...
Page 53: ...50 Section 3 Function Transition Charts ZX T Operation Manual Section 3 BASIC OPERATION ...
Page 103: ...100 Section 5 Error Output Function ZX T Operation Manual Section 5 DETAILED SETTINGS ...
Page 113: ...110 Section 6 Initializing Settings Data ZX T Operation Manual Section 6 AUXILIARY FUNCTIONS ...