Table D.6 Recommended Input Fuse Selection
VZA
Fuse Type
Fuse
Fuse Ampere Rating
200 V Class Single-Phase Drives
B0P1
Time Delay Class RK5 Fuses
600 Vac, 200 kAIR
TRS5R
5
B0P2
TRS10R
10
B0P4
TRS20R
20
B0P7
TRS35R
35
B1P5
TRS50R
50
B2P2
TRS60R
60
B4P0
Non-Time Delay Class J
Fuses
600 Vac, 200 kAIR
A6T100
100
200 V Class Three-Phase Drives
20P1
Time Delay Class RK5 Fuses
600 Vac, 200 kAIR
TRS5R
5
20P2
TRS5R
5
20P4
TRS10R
10
20P7
TRS15R
15
21P5
TRS25R
25
22P2
TRS35R
35
24P0
TRS60R
60
25P5
Non-Time Delay Class J
Fuses
600 Vac, 200 kAIR
A6T110
110
27P5
A6T150
150
2011
A6T200
200
2015
A6T225
225
400 V Class Three-Phase Drives
40P2
Time Delay Class RK5 Fuses
600 Vac, 200 kAIR
TRS2.5R
2.5
40P4
TRS5R
5
40P7
TRS10R
10
41P5
TRS20R
20
42P2
TRS20R
20
43P0
TRS20R
20
44P0
TRS30R
30
45P5
Non-Time Delay Class J
Fuses
600 Vac, 200 kAIR
A6T60
60
47P5
A6T70
70
4011
A6T110
110
4015
A6T125
125
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class
2 (UL regulations) power supply for the control circuit terminal.
Table D.7 Control Circuit Terminal Power Supply
Input / Output
Terminal Signal
Power Supply Specifications
Multi-function photocoupler output
P1, P2, PC
Require class 2 power supply
Multi-function digital inputs
S1, S2, S3, S4, S5, S6, SC
Use the internal power supply of the drive. Use class 2
for external power supply.
Multi-function analog inputs
A1, A2, AC
Use the internal power supply of the drive. Use class 2
for external power supply.
Pulse train input
RP
Use the internal LVLC power supply of the drive. Use
class 2 for external power supply.
Pulse train output
MP
Use the internal LVLC power supply of the drive. Use
class 2 for external power supply.
n
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current
flow will not rise above 30,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the
power supply being used.
• Suitable for use on a circuit capable of delivering not more than 30,000 RMS symmetrical amperes for 240 V in 200 V
class drives (up to 480 V for 400 V class drives) motor overload protection.
u
Drive Motor Overload Protection
Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor
overload protection is UL listed and in accordance with the NEC and CEC.
D.3 UL Standards