Item
Specification
Environment
Storage/Installation Area
Indoors
Ambient Temperature
-10 to +40 °C (wall-mounted enclosure)
-10 to +50 °C (open chassis)
Humidity
95% RH or less with no condensation
Storage Temperature
-20 to +60 °C allowed for short-term transport of the product
Altitude
1000 m or less
Shock, Impact
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
2
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Orientation
Install the drive vertically to maintain maximum cooling effects
Safety Regulations and Standards
Safe Disable Input according to UL508C, EN954-1 Safety Category 3; EN61508, SIL2;
Time from input open to drive output stop is less than 1 ms.
Protective Enclosure
VZA
4P0 drives and smaller: Open chassis/IP20
VZA
5P5 drives and larger: Open chassis/NEMA 1
Cooling Method
VZAB0P1 to B0P7: self-cooled
VZAB1P5 to B4P0: cooling fan
VZA20P1 to 20P4: self-cooled
VZA20P7 to 2015: self-cooled
VZA40P2 to 40P7: self-cooled
VZA41P5 to 4015: self-cooled
<1> Speed control accuracy varies somewhat according to the type of motor and drive settings.
<2> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor
speed down to zero in the shortest time.
<3> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a braking resistor or the Braking
Resistor Unit. The default setting for the stall prevention function will interfere with the braking resistor.
<4> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<5> Parameter settings allow up to 150 V.
<6> A Momentary Power Loss Ride-Thru Unit is required for 200/400 V class drives 7.5 kW and less if the application needs to continue running
during a momentary power loss up to 2 seconds.
<7> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the motor windings during run: Low
ground resistance for the motor cable and terminal block; low ground resistance for the motor cable and terminal block; or the drive is powered
up from a ground short.
A.4 Drive Specifications
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
293
A
Specifications
7/16/2008-13:23