5.10 o: Operator Related Settings
These parameters concern the various functions and features of the digital operator.
u
o1: Display Settings and Selections
These parameters determine how data is shown on the operator display.
n
o1-01: Drive Mode Unit Monitor Selection
Selects which U
-
monitor parameter will be displayed in the operation menu upon power-up when o1-02 = 5. Press
the up arrow key four times and select the desired monitor.
No.
Name
Setting Range
Default
o1-01
Drive Mode Unit Monitor Selection
104 to 621
(U1-04 to U6-21)
<1>
106 (U1-06)
<1> U2-
and U3-
parameters cannot be selected.
To select a monitor parameter, set the three numeric digits that make up that monitor. This is done by entering the
-
part of U
-
. For a list of monitors,
Refer to U: Monitor Parameters on page 219
.
n
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the
drive is first turned on.
No.
Name
Setting Range
Default
o1-02
User Monitor Selection after Power Up
1 to 5
1
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward/Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Selected Monitor (set by o1-01)
n
o1-03: Digital Operator Display Selection
Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
• U1-01: frequency reference
• U1-02: output frequency
• U1-05: motor speed
• U1-16: output frequency after softstarter (accel/decel ramp generator)
• d1-01 to d1-17: frequency references
No.
Name
Setting Range
Default
o1-03
Digital Operator Display Selection
0 to 3
0
Setting 0: Hz
The frequency reference and monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %
The frequency reference and monitors are displayed as a percentage with a resolution of 0.01%. 100% is equal to the
maximum output frequency.
Setting 2: r/min
The frequency reference and monitors are displayed in r/min with a resolution of 1 r/min. For correct display values, the
number of motor poles must be entered into parameters E2-04, E4-04, or E5-04, depending on which motor setting is used.
Setting 3: User-Set Display Units
The frequency reference and monitors are displayed with the maximum value and resolution defined by parameters o1-10
and o1-11. The default display unit when o1-03 = 3 is 100.00%.
5.10 o: Operator Related Settings
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
213