Min. output
frequency
100%
(Max. output
frequency)
Output frequency
when Stop command
is entered
Operation wait time
t
Selected
decel time
Minimum
Baseblock Time
(L2-03)
Figure 5.9 Operation Wait Time Depending on Output Frequency
Setting 9: Simple Positioning Stop
This method of stopping the motor always decelerates the same distance to stop as shown in
Figure 5.10
. The stopping
distance S1 is calculated using the maximum output frequency setting E1-04 and the selected deceleration time. If the
drive is stopped from a frequency lower than the maximum speed it keeps the current speed. When the distance traveled
becomes equal to S1 - S2, the drive decelerates to stop using the current deceleration time. The stopping accuracy can be
adjusted using the positioning gain set in parameter d4-12.
S1
S1
t
S1
t
S2
Max. output
frequency
Deceleration
distance
Motor speed
Max. output
frequency
Deceleration
distance
Motor speed
Normal Deceleration
Simple Positioning
Set deceleration time
Run command
Set deceleration time
Run command
Figure 5.10 Simple Positioning Deceleration
Precautions when using Simple Positioning:
• Changing the deceleration time during the deceleration will result in inaccurate positioning as the calculation considers
the deceleration time that was active only when the Run command was removed.
• The Dwell function must be deactivated (b6-03 and b6-04 = 0).
• The KEB function can not be used (H1-
must be different than 65/66/7A/7B).
• The Stall Prevention during stop must be deactivated (L3-04 = 0). For regenerative loads a braking option might be
necessary.
• The overvoltage suppression must be disabled (L3-11 = 1).
• High Slip Braking must be deactivated (H1-
must be different from 68).
• The S-curves at deceleration start and deceleration end must be inactive (C2-03/04 = 0).
n
b1-04: Reverse Operation Selection
For some applications, reverse motor rotation is not appropriate and may even cause problems (e.g., air handling units,
pumps, etc.). Setting parameter b1-04 to 1 instructs the drive to ignore any Reverse run commands.
No.
Parameter Name
Setting Range
Default
b1-04
Reverse Operation Selection
0 or 1
0
Setting 0: Reverse Operation Enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse Operation Disabled
Drive disregards a Reverse run command or a negative frequency reference.
n
b1-07: LOCAL/REMOTE Run Selection
The drive has the following three separate control sources that can be switched using digital inputs or the LO/RE key on
the digital operator (for details
Refer to Setting 1: LOCAL/REMOTE Selection on page 161
,
Refer to Setting 2: External
Reference 1/2 Selection on page 161
and
Refer to o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection on page
214
):
5.2 b: Application
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
107
5
Parameter Details
7/16/2008-13:23