No.
Name
Description
Range
Def.
Control
Mode
Addr. Hex Pg.
V/f OL
V PM
E1-04
Max Output
Frequency
These parameters are only applicable when E1-03 is set to
F. To set linear V/f characteristics, set the same values for
E1-07 and E1-09. In this case, the setting for E1-08 will be
disregarded. Ensure that the four frequencies are set
according to these rules:
E1-04 ≥ E1-06> E1-07 ≥ E1-09
E1-09 E1-07 E1-06 E1-11 E1-04
E1-05
E1-12
E1-13
E1-08
E1-10
VACrms Out(V)
Frequency (Hz)
40.0 to
400.0
<21>
50 Hz
<10>
S
S
S
303
146
E1-05
<24>
Max Output
Voltage
0.0 to 255.0
200 V
<10>
S
S
S
304
146
E1-06
Base Frequency
0.0 to
E1-04
50 Hz
<10>
S
S
S
305
146
E1-07
Mid Output
Frequency
0.0 to
E1-04
2.5 Hz
<2>
A
A
-
306
146
E1-08
<24>
Mid Output
Frequency Voltage
0.0 to 255.0
16.0 V
<2>
<12>
A
A
-
307
146
E1-09
Minimum Output
Freq.
0.0 to
E1-04
1.3 Hz
<2>
<10>
S
S
S
308
146
E1-10
<24>
Minimum Output
Freq. Voltage
0.0 to 255.0
12.0 V
<2>
<12>
A
A
-
309
146
E1-11
<26>
Mid Output
Frequency 2
0.0 to
E1-04
0.0 Hz
A
A
-
30A
146
E1-12
<24>
<26>
Mid Output
Frequency Voltage
2
0.0 to 255.0 0.0 V
A
A
-
30B
146
E1-13
<24>
Base Voltage
0.0 to 255.0 0.0 V
A
S
-
30C
146
E2: Motor Parameters
Use E2 parameters to set motor-related data.
E2-01
Motor Rated
Current
Sets the motor nameplate full load current in amperes (A).
Automatically set during Auto-Tuning.
10 to 200%
of drive
rated
current
<27>
<57>
S
S
−
30E
147
E2-02
Motor Rated Slip
Sets the motor rated slip in Hertz.
Automatically set during rotational Auto-Tuning.
0.00 to
20.00
<57>
A
A
−
30F
147
E2-03
Motor No-Load
Current
Sets the magnetizing current of the motor in Ampere.
Automatically set during rotational Auto-Tuning.
0 to less
than E2-01
<57>
A
A
−
310
147
E2-04
Number of Motor
Poles
Sets the number of motor poles. Automatically set during
Auto-Tuning.
2 to 48
4 poles
A
A
−
311
148
E2-05
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance in ohms.
Automatically set during Auto-Tuning.
0.000 to
65.000
<37>
<57>
A
A
−
312
148
E2-06
Motor Leakage
Inductance
Sets the voltage drop due to motor leakage inductance as a
percentage of motor rated voltage.
Automatically set during Auto-Tuning.
0.0 to 40.0
<57>
A
A
−
313
148
E2-07
Motor Iron-Core
Saturation
Coefficient 1
Sets the motor iron saturation coefficient at 50% of
magnetic flux. Automatically set during Auto-Tuning.
E2-07 to
0.50
0.50
−
A
−
314
148
E2-08
Motor Iron-Core
Saturation
Coefficient 2
Sets the motor iron saturation coefficient at 75% of
magnetic flux. Automatically set during Auto-Tuning.
E2-07 to
0.75
0.75
−
A
−
315
148
E2-09
Motor Mechanical
Loss
Sets the motor mechanical loss as a percentage of motor
rated power (kW). Adjust in the following circumstances:
When there is a large amount of torque loss due to motor
bearing friction.
When there is a large amount of torque loss.
0.0 to 10.0
0.0%
−
A
−
316
148
E2-10
Motor Iron Loss for
Torque
Compensation
Sets the motor iron loss in watts (W).
0 to 65535
<57>
A
−
−
317
148
E2-11
Motor Rated Output
Sets the motor rated power in kilowatts (kW).
Automatically set during Auto-Tuning. (1 HP = 0.746 kW).
0.00 to
650.00
0.40 kW
<12>
S
S
−
318
149
E2-12
Motor Iron-Core
Saturation
Coefficient 3
Set to the motor iron saturation coefficient at 130% of
magnetic flux.
Automatically set during rotational Auto-Tuning.
1.30 to 5.00
1.30
−
A
−
328
149
E3: Motor 2 V/f Characteristics
Use E3 parameters to set the V/f pattern for a second motor.
E3-01
Motor 2 Control
Method
0: V/f Control
2: Open Loop Vector (OLV)
0 or 2
0
A
A
−
319
149
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
309
B
Parameter List
7/16/2008-13:23