No.
Name
Description
Analog Output
Level
Unit
Control
Mode
Addr.
Hex
V/f O
LV
P
M
U1-04
Control Mode
Control method set in A1-02.
0: V/f without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
No output signal
available
–
A A A
43
U1-05
Motor Speed
Displays the motor speed feedback. Display units are
determined by o1-03.
10 V: Maximum
speed
0.01
Hz
– A –
44
U1-06
Output Voltage Reference
Displays the output voltage.
10 V: 200 Vrms
(400 Vrms)
0.1 V A A A
45
U1-07
DC Bus Voltage
Displays the DC bus voltage.
10 V: 400 V (800
V)
1 V
A A A
46
U1-08
Output Power
Displays the output voltage (this value is determined
internally).
10 V: Drive
capacity (kW)
(rated motor
capacity)
<27>
A A A
47
U1-09
Torque Reference
Monitor of internal torque reference value for Open Loop
Vector (OLV) control
10 V: Motor rated
torque
–
– A –
48
U1-10
Input Terminal Status
Displays the input terminal status.
Digital input terminal
S1 enabled
Digital input terminal
S2 enabled
Digital input terminal
S3 enabled
Digital input terminal
S4 enabled
Digital input terminal
S5 enabled
Digital input terminal
S6 enabled
No output signal
available
–
A A A
49
U1-11
Output Terminal Status
Displays the output terminal status.
Multi-Function
Digital Output (fault)
(terminal MA/MB-MC)
Multi-Function
Digital Output 1
(terminal P1) enabled
Multi-Function
Digital Output 2
(terminal P2) enabled
No output signal
available
–
A A A
4A
U1-12
Drive Status
Verifies the drive operation status.
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
No output signal
available
–
A A A
4B
U1-13
Terminal A1 Input Level
Displays analog input A1 level: 100% when input is 10 V. 10 V: 100%
0.1% A A A
4E
U1-14
Terminal A2 Input Level
Displays analog input A1 level: 100% when input is 10 V.. 10 V: 100%
0.1% A A A
4F
U1-16
Output Frequency after Soft
Starter
Displays output frequency with ramp time and S-curves.
Units determined by o1-03.
10 V: Max
frequency
0.01
Hz
A A A
53
U1-18
OPE Fault Parameter
Displays parameter no. for oPE
or Err where error
occurred.
No output signal
available
–
A A A
61
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
333
B
Parameter List
7/16/2008-13:23