When viewing the settings for H4-02, terminal AM will output a voltage that is equal to 100% of the monitor value
(considering the present setting). When viewing the settings for H4-03, terminal AM will output a voltage that is equal to
0% of the monitor value.
u
H5: MEMOBUS/Modbus Serial Communication
Through the drives built in RS-422/485 port (terminals R+, R-, S+, S-), serial communication can be performed with
programmable logic controllers (PLCs) or similar devices using the MEMOBUS/Modbus protocol.
The H5-
parameters are used to set up the drive for MEMOBUS/Modbus Communications.
Refer to MEMOBUS/
Modbus Serial Communication on page 358
for detailed descriptions of the H5-
parameters.
u
H6: Pulse Train Input/Output
A one track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse
train signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control.
The pulse output monitor terminal MP, which can be used in sinking or sourcing mode, can output drive monitors values
as a pulse train signal with a maximum frequency of 32 kHz.
Use parameters H6-
to scale and set up the function for the pulse input terminal RP and pulse output terminal MP.
n
H6-01: Pulse Train Input Terminal RP Function Selection
Selects the function of pulse train input terminal RP.
No.
Name
Setting Range
Default
H6-01
Pulse Train Input Terminal RP Function Selection
0 to 4
0
Setting 0: Frequency Reference
If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01/15 = 4), the drive
reads the frequency value from terminal RP.
Setting 1: PID Feedback Value
Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP.
Refer to b5: PID
Control on page 115
for details on PID control.
Setting 2: PID Setpoint Value
Using this setting, the setpoint value for PID control can be supplied as a pulse signal at terminal RP.
Refer to b5: PID
Control on page 115
for details on PID control.
Setting 3: Speed Feedback for V/f Control (V/f Control only, Motor 1 only)
This setting enables simple speed feedback for V/f Control. A pulse signal can be used to input the motor speed to the
drive and thereby improve the speed control accuracy. Note that this speed feedback can only be a one track signal that
can not be used for direction detection. The drive needs a separate motor rotation direction signal.
Refer to C5: Automatic
Speed Regulator (ASR) on page 129
for details on using Simple V/f Control with Speed Feedback.
n
H6-02: Pulse Train Input Terminal RP Scaling
The pulse train input scaling parameter sets the terminal RP input frequency that is equal to 100% of the signal selected
as the input value in parameter H6-01.
No.
Name
Setting Range
Default
H6-02
Pulse Train Input Scaling
1000 to 32000 Hz
1440 Hz
n
H6-03: Pulse Train Input Terminal RP Gain
Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to terminal
RP.
No.
Name
Setting Range
Default
H6-03
Pulse Train Input Gain
0.0 to 1000.0%
100.0%
n
H6-04: Pulse Train Input Terminal RP Bias
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
No.
Name
Setting Range
Default
H6-04
Pulse Train Input Bias
-100.0 to 100.0%
0.0%
n
H6-05: Pulse Train Input Terminal RP Filter Time
Sets the pulse train input filter time constant in seconds.
5.7 H: Terminal Functions