No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
o3-01 Copy Function Selection
Selects the copy function operation.
0: No action
1: READ
2: COPY
3: VERIFY
NOTE:
When using the copy function, the drive model
number (o2-04) and the software number (U1-14) must
match or an error will occur.
0 to 3
0
A A A
515
—
o3-02 Copy Function READ
Permission
Locks the READ operation to prevent accidental overwriting
of the data stored in the LED operator.
0: READ operation prohibited
1: READ operation allowed
0, 1
0
A A A
516
—
o4: Maintenance Period
Use o4 parameters to perform maintenance.
o4-01
Accumulated Operation
Time Setting
Sets the value for the cumulative operation time of the drive
in units of 10 h.
0 to 9999
0
A A A
50B
216
o4-02
Accumulated Operation
Time Selection
Determines, how the cumulative operation time (U4-01) is
counted.
0: Logs power-on time
1: Logs operation time when the drive output is active (output
operation time).
0 to 1
0
A A A
50C
216
o4-03
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in
units of 10 h.
<61>
0 to 9999
0
A A A
50E
216
o4-05
Capacitor Maintenance
Setting
Sets the value of the capacitor maintenance time monitor
U4-05.
0 to 150
0%
A A A
51D
217
o4-07
Soft Charge Bypass Relay
Maintenance Setting
Sets the value of the Soft Charge Bypass Relay Maintenance
monitor U4-06.
0 to 150
0%
A A A
523
217
o4-09
IGBT Maintenance Setting
Sets the value of the IGBT Maintenance monitor U4-07.
0 to 150
0%
A A A
525
217
o4-11
U2, U3 Initialize Selection
Selects if U2-
(Fault Trace), U3-
(Fault History)
monitors are reset at drive initialization.
0: Saves the fault monitor data
1: Resets the fault monitor data
0 to 1
0
A A A
510
217
o4-12
kWh Monitor Initialize
Selection
Selects if U4-10 and U4-11 (kWh monitor) are reset at drive
initialization.
0: Saves the U4-10 and U4-11 monitor data.
1: Resets the U4-10 and U4-11 monitor data.
0 to 1
0
A A A
512
217
o4-13
Number of Run Commands
Initialize Selection
Selects if the Run command counter (U4-02) is reset at drive
initialization.
0: Saves the number of Run commands
1: Resets the number of Run commands
0 to 1
0
A A A
528
217
<9> Default setting value is dependent on parameter E1-01, Input Voltage Setting.
<11> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<22> Parameter can be changed during run.
<61> Valid for drive software 1011 and later. Value is set in 1 h units for older software.
u
q: FBDs Parameters
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
q1-01 to
q6-07 FBDs Parameters
Reserved for FBDs.
-
-
A A Α
-
—
u
r: FBDs Connection Parameters
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
r1-01
FBDs Connection Parameter
1 (upper)
Parameter 1 for connecting FBDs (upper).
0 to
FFFFH
0
– A A
1840
—
r1-02
FBDs Connection Parameter
1 (lower)
Parameter 1 for connecting FBDs (lower).
0 to
FFFFH
0
– A A
1841
—
r1-03
FBDs Connection Parameter
2 (upper)
Parameter 2 for connecting FBDs (upper).
0 to
FFFFH
0
– A A
1842
—
r1-04
FBDs Connection Parameter
2 (lower)
Parameter 1 for connecting FBDs (lower).
0 to
FFFFH
0
– A A
1843
—
B.2 Parameter Table
330
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23