Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
C1-07
setting
When the output frequency ( C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)
C1-01
setting
C1-02
setting
C1-08
setting
Figure 5.24 Accel/Decel Time Switching Frequency
Switching Acceleration and Deceleration Times by Motor Selection
When switching between motor 1 and 2 using a digital input (H1-
= 16) parameters C1-01 to C1-04 become accel/
decel time 1/2 for motor 1 and C1-05 to C1-08 become accel/decel time 1/2 for motor 2. In this case the digital input
“Accel/Decel Time 2 Selection” can not be used (this would trigger an oPE03 error, indicating a contradictory multi-
function input settings).
Table 5.10
explains the activation of accel/decel times depending on the motor selection and accel/decel time selection.
Table 5.10 Motor Switching and Accel/Decel Time Combinations
Accel/Decel Time 1 (H1-
= 7)
Motor 1 Selected
Motor 2 Selected
Accel
Decel
Accel
Decel
Open
C1-01
C1-02
C1-05
C1-06
Closed
C1-03
C1-04
C1-07
C1-08
n
C1-09: Fast-stop Time
Parameter C1-09 will set a special deceleration that is used when certain faults occur or that can be operated by closing a
digital input configured as H1-
= 15 (N.O. input) or H1-
= 17 (N.C. input). The input does not have to be closed
continuously, even a momentary closure will trigger the Fast-stop operation.
Unlike standard deceleration, once the Fast-stop operation is initiated, the drive cannot be restarted until the deceleration
is complete, the Fast-stop input is cleared, and the Run command is cycled.
A digital output programmed for “During Fast-stop” (H2-01/02/03 = 4C) will be closed as long as Fast-stop is active.
No.
Parameter Name
Setting Range
Default
C1-09
Fast-stop Time
0.0 to 6000.0 s
<1>
10.0 s
<1> The setting range for the acceleration and deceleration times is determined by C1-10 (Accel/Decel Time Setting Units). For example, if the
time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid
this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast-stop time to C1-09.
n
C1-10: Accel/Decel Time Setting Units
Determines the units for the acceleration and deceleration times set to C1-01 through C1-09 using parameter C1-10.
No.
Parameter Name
Setting Range
Default
C1-10
Accel/Decel Time Setting Units
0 or 1
1
Setting 0: 0.01 s Units
The accel/decel. times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. If any of the parameters C1-01 to
C1-09 is set to 600.1 seconds or more, then C1-10 cannot be set to 0.
Setting 1: 0.1 s Units
The accel/decel. times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.
n
C1-11: Accel/Decel Switch Frequency
Sets the switching frequency for automation accel/decel. time change over.
Refer to Switching Accel/decel Times by a
Frequency Level on page 125
.
No.
Parameter Name
Setting Range
Default
C1-11
Accel/Decel Switch Frequency
0.0 to 400.0 Hz
0.0 Hz
Note:
Setting C1-11 to 0.0 Hz disables this function.
5.3 C: Tuning
126
SIEP C710606 20 OYMC AC Drive - V1000 User Manual