61
4.
Forced outputs are possible only when the counting flag is OFF.
5.
Normal operation is returned to when the start signal is set during forced
output.
6.
Forced outputs becomes inoperative during normal operation.
7.
When RESET COUNTER is set during a forced output, the external out
put is momentarily turned OFF, then restored to the status designated
by the relevant force bit.
4-3-5
Application Example
Measuring and Cutting Rod System Configuration
Counter Unit
C200H PC
Output #4
Cutter
Output #0
Output #1
Output #2
Motor Controller
Output
Motor ON
High/low
speed
Brake
Motor
Encoder
Bobbin
An encoder adapter is required
if the C200H-CT002 is used
with an open-collector encoder.
Inputs A and B
Outputs #0 through #2, and #4
Encoder adapter
Operation
A specific length wire rod is fed in and cut using the following controlling pro-
cedure.
1, 2, 3... 1.
The motor is started at a low speed and the brake is turned OFF.
2.
The motor speed is increased.
3.
The motor speed is decreased just before the designated position.
4.
The motor is stopped, taking the distance the motor moves by inertia
into consideration.
5.
The brake is turned ON immediately before the designated position.
6.
The cutter is activated at the designated position.
Preset Mode
Section 4-3
Summary of Contents for SYSMAC C200H-CT001-V1
Page 1: ...Cat No W141 E1 4 High speed Counter Units SYSMAC C200H CT001 V1 CT002 OPERATION MANUAL...
Page 2: ......
Page 3: ...C200H CT001 V1 CT002 High speed Counter Units Operation Manual Revised September 2000...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ......
Page 10: ......
Page 20: ......
Page 46: ......
Page 96: ......
Page 98: ......