Switch Settings
In this example, the unit number selector is set to 1 and the mode selector is
set to 5. All pins except number 1 are turned OFF on the back panel DIP
switch to designate increment/decrement inputs.
Wiring
1, 2, 3... 1.
Connect the photoelectric switch outputs to input A (increment) and the
input B (decrement).
2.
Connect the count switch to control input IN1.
3.
Connect the latch switch to control input IN2.
DM Area Settings
DM 1100
DM 1101
0
0
5
0
0
0
0
0
Sets the mode to 5 (latch).
Designates use of control input IN1 from the
connector (not the internal IN1).