IN1 and IN2 may originate either externally or internally. This mode does not
support external outputs from the Counter Unit or data transfer.
Sampling Mode
In sampling mode, pulses are counted for a preset interval after control input
IN1 (the count signal) is turned ON. Counting may be in either direction.
Counting always begins at zero and ranges between –8,388,608 and
8,388,607. The time interval must be between 10 and 9,999 ms.
Control input IN1 may originate either externally or internally. This mode does
not support external outputs from the Counter Unit or data transfer.
Operating Modes
Section 1-4