![background image](http://html.mh-extra.com/html/omron/sysmac-c200h-ct001-v1/sysmac-c200h-ct001-v1_operation-manual_742017076.webp)
62
ÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉ
ON
OFF
High
speed
Low
speed
ON
OFF
ON
OFF
Parameter
Present counter value
A
B
C
D
E
T
Setting (ms)
10,000
100
150
200
0
50
500
A
C
T
B
E
Current counter value
Counter preset value
Motor drive (Output #0)
High/Low speed (Output #1)
Brake (Output #2)
Cutter (Output #4)
Setting example
Switch Settings
In this example, the unit number switch is set to 1 and the mode switch is set
to 3. Pins 3 and 8 are turned ON on the back-panel DIP switch to designate
offset phase inputs with a x2 input multiplier and to enable RESET COUNT-
ER. All other pins on the DIP switch are turned OFF.
Wiring
1, 2, 3... 1.
Connect encoder outputs to inputs A and B.
2.
Connect outputs #0, #1, and #2 to the motor controller inputs as follows:
#0: motor start switch; #1: high/low speed switch; #2: brake sig-
nal.
3.
Connect output #4 to the input terminal of the cutter driver.
DM Area Settings
DM 1100
DM 1101
DM 1102
DM 1103
DM 1104
DM 1105
DM 1106
DM 1107
DM 1108
DM 1109
DM 1110
DM 1111
DM 1112
DM 1113
DM 1114
3
0
0
0
0
1
0
0
0
0
5
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5
0
0
0
0
0
5
0
–
–
–
–
–
–
0
0
0
0
0
0
0
0
0
0
0
0
2
0
–
0
–
DM 1115
1
0
0
1
Sets mode no. 3.
A = 100
B = 150
C = 200
D = 0
E = 50
T = 500 ms
Preset = 10000
Output #4 only
Preset Mode
Section 4-3
Summary of Contents for SYSMAC C200H-CT001-V1
Page 1: ...Cat No W141 E1 4 High speed Counter Units SYSMAC C200H CT001 V1 CT002 OPERATION MANUAL...
Page 2: ......
Page 3: ...C200H CT001 V1 CT002 High speed Counter Units Operation Manual Revised September 2000...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ......
Page 10: ......
Page 20: ......
Page 46: ......
Page 96: ......
Page 98: ......