Specifications
Appendix B
88
C200H-CT002 Input Specifications
Item
Inputs A, B, and Z
Control inputs IN1 and IN2
Input voltage
5 VDC
10%
12 or 24
VDC
10%
Input current
4 to 7 mA
4 to 13 mA
ON voltage (min.)
Same as the RS-422 line driver (Am26LS31-compatible).
4.5 VDC
10.2 VDC
OFF voltage (max.)
2.0 VDC
3.0 VDC
ON/OFF response
time
1 ms max.
Minimum response
time
*Input A and B
Waveform at positive terminals 75 kHz, 50% pulse
ON
0V
OFF
Relation between inputs A and B for offset phase Inputs
ON
Input A 0V
OFF
ON
Phase B 0V
OFF
T1 T2
T1, T2: 3
µ
s min.
There must be at least a 3
µ
s interval between the change
point of input A and that of input B.
*Input Z
A pulse width of at least 10
µ
s is required.
10
µ
s min.
10
µ
s min.
ON
0V
OFF
ON
OFF
0.1 ms max.
Note:
These signals must re-
main ON for at least the
length of the PC’s cycle
time to be accurately
read from the PC.