11
Row B
Pin no.
Row A
20
Input A: neg.
19
Input A: pos.
18
Input B: neg.
17
Input B: pos.
16
Input Z: neg.
15
Input Z: pos.
14
13
Control input IN1: 12/24 VDC
Control input IN1: 0 V
12
Control input IN1: 5 VDC
11
Control input IN2: 12/24 VDC
Control input IN2: 0 V
10
Control input IN2: 5 VDC
9
Outputs 0 through 3
Power supply: 5 to 24 VDC
8
Output 0
7
Output 1
Outputs 0 through 3, COM: 0 V
6
Output 2
5
Output 3
Outputs 4 through 7
Power supply: 5 to 24 VDC
4
Output 4
3
Output 5
Outputs 4 through 7, COM: 0 V
2
Output 6
1
Output 7
Wiring Connectors
Solder-type connectors are included with the Counter Unit.
Use wire with a cross-sectional area of 0.3 mm
2
or less. When soldering, do not
short-circuit an adjacent terminal; cover the soldered section with an insulation
tube. When using multicore cable, wire output and input cables separately.
Connector
Wire
Insulation tube
C200H-CT002
Wiring
Section 2-2