37
DM Area
The DM area contains user parameters that are to be set into the Counter
Unit, including the operating mode and output range limits. The first DM word
for each Counter Unit is indicated by m and equals 1,000 plus 100 times the
unit number.
Word
Bit
Function
m
07 through 00
Set to 0.
11 through 08
Operating mode (Here, either 1: linear or 2: circular)
15 through 12
Set to 0.
m + 1
15 through 00
Effective range bits (bit numbers correspond to range numbers)
m + 2
15 through 00
Maximum counter value (for circular mode only)
m + 3
15 through 00
6 digits (Bits 15 to 04 not used.)
m + 4
m + 9
Not used.
m + 10
15 through 00
Lower limit for range #0, 7 digits with sign digit
m + 11
15 through 00
m + 12
15 through 00
Upper limit for range #0, 7 digits with sign digit
m + 13
15 through 00
m + 14
15 through 00
Output pattern for range #0 (bit numbers correspond to output numbers)
m + 15
m + 19
Lower limit, upper limit, and output pattern for range #1 (Format same as
that for range #0.)
m + 20
m + 24
Lower limit, upper limit, and output pattern for range #2 (Format same as
that for range #0.)
m + 25
m + 29
Lower limit, upper limit, and output pattern for range #3 (Format same as
that for range #0.)
m + 30
m + 34
Lower limit, upper limit, and output pattern for range #4 (Format same as
that for range #0.)
m + 35
m + 39
Lower limit, upper limit, and output pattern for range #5 (Format same as
that for range #0.)
m + 40
m + 44
Lower limit, upper limit, and output pattern for range #6 (Format same as
that for range #0.)
m + 45
m + 49
Lower limit, upper limit, and output pattern for range #7 (Format same as
that for range #0.)
m + 50
m + 54
Lower limit, upper limit, and output pattern for range #8 (Format same as
that for range #0.)
m + 55
m + 59
Lower limit, upper limit, and output pattern for range #9 (Format same as
that for range #0.)
m + 60
m + 64
Lower limit, upper limit, and output pattern for range #10 (Format same as
that for range #0.)
m + 65
m + 69
Lower limit, upper limit, and output pattern for range #11 (Format same as
that for range #0.)
m + 70
m + 74
Lower limit, upper limit, and output pattern for range #12 (Format same as
that for range #0.)
m + 75
m + 79
Lower limit, upper limit, and output pattern for range #13 (Format same as
that for range #0.)
m + 80
m + 84
Lower limit, upper limit, and output pattern for range #14 (Format same as
that for range #0.)
m + 85
m + 89
Lower limit, upper limit, and output pattern for range #15 (Format same as
that for range #0.)
m + 89
m + 99
Not used.
Linear and Circular Modes
Section 4-2
Summary of Contents for SYSMAC C200H-CT001-V1
Page 1: ...Cat No W141 E1 4 High speed Counter Units SYSMAC C200H CT001 V1 CT002 OPERATION MANUAL...
Page 2: ......
Page 3: ...C200H CT001 V1 CT002 High speed Counter Units Operation Manual Revised September 2000...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ......
Page 10: ......
Page 20: ......
Page 46: ......
Page 96: ......
Page 98: ......