![background image](http://html.mh-extra.com/html/omron/sysmac-c200h-ct001-v1/sysmac-c200h-ct001-v1_operation-manual_742017035.webp)
21
2-3-2
C200H-CT002
The following wiring examples shows connections between a line-driver en-
coder (Am26LS31-compatible) with outputs A, B, Z and inputs A, B, and Z.
E
Input A
Input B
Input Z
Shielded twisted pair cable
+
–
Encoder
–
+
–
+
Power supply
C200H-CT002 Counter Unit
A+
A–
B+
B–
C+
C–
The following wiring example shows connections between an open-collector
encoder and an Encoder Adapter (C500-AE001), and between the Encoder
Adapter and inputs A, B, and Z. Connections should be wired so that Counter
Unit inputs go ON when encoder outputs go ON. Because the C500-AE001
Encoder Adapter uses an Am26LS31-compatible line driver, high voltage is
impressed on the positive terminal and low voltage is impressed on the nega-
tive terminal when the output is high.
E
Input A
Input B
Input Z
Shielded twisted pair cable
+
–
–
+
–
+
C200H-CT002 Counter Unit
E
Shielded
twisted
pair cable
C500-AE001 En-
coder Adapter
5- to
12-VDC
power
supply
A–
A+
B–
B+
Z–
Z+
V
CC
0 V
V
CC
0 V
V
CC
0 V
Encoder
Voltage
regulator
+
–
Example 1
Line-driver Encoder
Example 2
Open-collector Encoder
and Encoder Adapter
Input Circuit Wiring Examples
Section 2-3
Summary of Contents for SYSMAC C200H-CT001-V1
Page 1: ...Cat No W141 E1 4 High speed Counter Units SYSMAC C200H CT001 V1 CT002 OPERATION MANUAL...
Page 2: ......
Page 3: ...C200H CT001 V1 CT002 High speed Counter Units Operation Manual Revised September 2000...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ......
Page 10: ......
Page 20: ......
Page 46: ......
Page 96: ......
Page 98: ......