5 Setup and Wiring
5 - 42
Vision System FZ5 series Hardware Setup Manual (Z423)
• Make sure to tighten all installation screws securely.
• To keep proper air flow, keep the top of the FH Sensor Controller 50 mm or more apart from other
devices. Install the FH Sensor Controller with a clearance of 30 mm on the right and left side, and 15
mm for rear planes. The clearance is required for installing multiple units side-by-side.
Side Mounting
Bottom Mounting
Installation in a Control Panel
19.5
143
24
141
4-M4 depth 4.5 (mounting screw hole)
19.2
143
182.5
24
141
190
20.1
4-M4 depth 4.5 (mounting screw hole)
(Unit: mm)
• Left side
• Right side
* Recommended tightening torque: 1.2 N•m to 1.3 N•m
* The tolerance is ±0.2 mm.
38.1
26.7
148.5
10.5
94
66.2
4-M3 depth 4.5 (mounting screw hole)
Insulating leg: 4
• Bottom
(Unit: mm)
* Do not remove the Insulating leg. Fix the Insulating leg to secure the
ventilation path.
* Recommended tightening torque: 0.54 N•m to 0.6 N•m
* The tolerance is ±0.2 mm.