2-2. Wiring the Communication Cable
2-2-2. Connect a cable between CPU unit’s communication port of PLC and the vision sensor.
Recommended cable:
XW2Z-200T (2m)
XW2Z-500T (5m)
* If you make your own cable, its length must be 15 m or shorter.
2-2-1. Wiring the RS-232C Communication Cable as shown bellow.
To Visual Sensor
To PLC
Signal Pin
No.
FG 1
Pin
No.
Signal
SD(TXD)
2 2
SD(TXD)
RD(RXD)
3 3
RD(RXD)
RS(RTS)
4 4
RS(RTS)
CS(CTS)
5 5
CS(CTS)
SG(GND)
9 9
SG(GND)
2-9 Vision Sensor
F160-C10