2-6. Inverter setting
For performing DeviceNet Communication, the following parameters have to be set.
* The parameters shown here is incorporated into DeviceNet communication Unit when power is
turned ON.
For this reason, change of parameter must be made after turning OFF the source power.
2-6-1. 3G3M series Inverter Parameter Setting
Frequency command from option
(DeviceNet Communication Unit) is enabled
0
9
Frequency command
selection
n004
0
0
Factory
setting
Unit: Hz
0
Unit selection at
frequency command
selection/reference
n035
Input from option (DeviceNet
Communication Unit) is enabled
3
Operation command
selection
n003
Description
Setup
figure
Name
Parameter
constant No.
Concerning other parameters set depending upon operation conditions.
Concerning change and detail of parameter, check the following manuals.
I527-E1 3-1 Operation of Digital Operator
I539-E1 4-1 SYSDRIVE 3G3MV Series Set-up
2-6-2. 3G3RV series Inverter Parameter Setting
Description
Factory
setting
Setup
figure
Name
Parameter
constant No.
Free run stop/error detection
1
1
Operation selection at
communication error
F6-01
Detect always
0
0
Detection method selection
at communication outer
error input
F6-02
Free run stop/error detection
1
1
Operation selection at
communication outer error
input
F6-03
Operation command by Option Card
(DeviceNet communication card)
1
3
Operation command
selection
b1-02
0
1
Unit: Hz
0
Unit selection at frequency
command
selection/reference
o1-03
Frequency command by Option Card
(DeviceNet communication card)
3
Frequency command
setting
b1-01
Concerning other parameters set depending upon operation conditions.
Concerning change and detail of parameter, check the following manuals.
I532-E1 3-2 Digital Operator
I539-E1 4-2 SYSDRIVE 3G3RV Series Set-up
2-6 Inverter
3G3MV-A2
/-AB
/-A4
3G3RV-A2
/-A4
Summary of Contents for FB LIBRARY -
Page 1: ......
Page 14: ...2 1 Controller Link Unit CJ1W CLK21 V1...
Page 23: ...2 2 DeviceNet Slave DRT2 Series DRT2...
Page 31: ...2 3 Position Control Unit CJ1W NCF71...
Page 42: ...2 4 Position Control Unit CJ1W NC113 133 213 233 413 433...
Page 49: ...2 5 Position Control Unit CS1W NC113 133 213 233 413 433...
Page 57: ...2 6 Inverter 3G3MV A2 AB A4 3G3RV A2 A4...
Page 71: ...2 7 Servo Driver R88D WT WT H WT HL R7D AP H AP L...
Page 84: ...2 8 RFID ID Sensor V600 H...
Page 95: ...2 9 Vision Sensor F160 C10...
Page 105: ...2 10 2D Code Reader V530 R2000 R160 R150V3...
Page 118: ...2 11 Smart Sensor ZX SF11 ZX LD40 ZX LDA11 N...
Page 129: ...2 12 Temperature Controller E5ZN 2...
Page 139: ...2 13 Temperature Control Unit CJ1W TC001 101 003 103 002 102 004 104...