2-1-4. Transmission Rate Setting
Transmission rate = 2M bps, when SW1-1 and 1-2 to be set to OFF.
Set the Transmission Rate for node 1 and 2 as described on the left.
*As the factory default setting is 2M bps, it is not need to be set.
2-1-5. Terminal Resistance Setting
Set the Terminal Resistance Switch -> ON, using flat-blade
screw driver.
* The factory default setting is OFF.
2-1-6. Mounting the Unit
Configure CPU Uit, Power Supply Unit and CLK Unit.
CLK
CPU
Power
Supply
Unit
End Cover
Mount the unit as shown above and use sliders on the top and
bottom of the unit to fix the unit.
2-1-7. Wiring Communication Cable
Connect all shielded
wires to the terminal
board and on one
end of the network
directly ground it .
Use the specified communication cable (twisted pair cable) to connect the nodes by multi-
drop.
Terminal has a marking printed on it that indicates the signal wire. Connect the cable so that
signal wire and the marking should match. Markings indicate the signal wires as shown
below:
-
SHLD (shield)
None
White
BDL (communications data
low)
Black
BDH (communications data
high)
Line color
Signal name
Mark
BDH
BDL
SHLD
BDH
BDL
SHLD
2-1 Controller Link Unit
CJ1W-CLK21-V1
Summary of Contents for FB LIBRARY -
Page 1: ......
Page 14: ...2 1 Controller Link Unit CJ1W CLK21 V1...
Page 23: ...2 2 DeviceNet Slave DRT2 Series DRT2...
Page 31: ...2 3 Position Control Unit CJ1W NCF71...
Page 42: ...2 4 Position Control Unit CJ1W NC113 133 213 233 413 433...
Page 49: ...2 5 Position Control Unit CS1W NC113 133 213 233 413 433...
Page 57: ...2 6 Inverter 3G3MV A2 AB A4 3G3RV A2 A4...
Page 71: ...2 7 Servo Driver R88D WT WT H WT HL R7D AP H AP L...
Page 84: ...2 8 RFID ID Sensor V600 H...
Page 95: ...2 9 Vision Sensor F160 C10...
Page 105: ...2 10 2D Code Reader V530 R2000 R160 R150V3...
Page 118: ...2 11 Smart Sensor ZX SF11 ZX LD40 ZX LDA11 N...
Page 129: ...2 12 Temperature Controller E5ZN 2...
Page 139: ...2 13 Temperature Control Unit CJ1W TC001 101 003 103 002 102 004 104...