Refer to
2-24-6. Muting Statistics Information
Standard Muting Mode
Exit-Only Muting Mode
Position Detection Muting Mode
Dynamic Muting
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Setting the muting time limit to infinite may cause a failure of the muting sensors to go undetected, resulting in the F3SG-RA
in an unintended muting state. Conduct risk assessment analysis thoroughly before enabling this setting.
Setting the muting input time limit value (maximum) to infinite may cause a failure of the muting sensors to go
undetected, resulting in a failure of disabling the muting state. Conduct risk assessment analysis thoroughly before
enabling this setting.
Dynamic Muting can be used in conjunction with any of Standard, Exit-only and Position detection muting modes.
Refer to
Safety Light Curtain Configuration Tool for Model F3SG (SD Manager 2) User’s Manual
for more
information on setting this function by the Configuration Tool.
Function
Factory Default Setting
Available Parameters
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
min
: Muting input time limit value (minimum)
0.1 s
0.1 to 3.9 s in 0.1-s increments
T1
max
: Muting input time limit value (maximum)
4 s
0.2 to 60 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption 0.1 s
0.1 to 20 s in 0.1-s increments
Function
Factory Default Setting
Available Parameters
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
min
: Muting input time limit value (minimum)
0.1 s
0.1 to 3.9 s in 0.1-s increments
T1
max
: Muting input time limit value (maximum)
4 s
0.2 to 4 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption 0.1 s
0.1 to 4 s in 0.1-s increments
T4: Muting end wait time
1 s
0.1 to 20 s in 0.1-s increments
T5: Exit-only muting delay time
4 s
4 to 20 s in 0.1-s increments
Function
Factory Default Setting
Available Parameters
Muting zone
Bottom beam
All beams
any beam in 1-beam increments
Top beam
T1
max
: Muting input time limit value(maximum)
4 s
0.2 to 60 s in 0.1-s increments, or infinite
T2: Muting time limit
60 s
1 to 600 s in 1-s increments, or infinite
T3: Maximum allowable muting signal interruption 0.1 s
0.1 to 4 s in 0.1-s increments
Function
Factory Default Setting
Available Parameters
Dynamic muting
Disable
Enable/Disable
Dynamic muting measurement time
3 s
1 to 25 s in 0.1-s increments
Number of dynamic muting allowable beams
1
0 to 5 in 1-beam increments
Summary of Contents for F3SG-RA
Page 16: ...xiv Introduction F3SG R User s Manual...
Page 24: ...xxii Introduction F3SG R User s Manual...
Page 44: ...20 Chapter 1 List of Models F3SG R User s Manual Overview and Specifications...
Page 132: ...108 Chapter 2 Setting Recovery F3SG R User s Manual System Operation and Functions...
Page 208: ...184 Chapter 4 Wiring F3SG R User s Manual Wiring Installation...
Page 244: ...220 Chapter 6 Maintenance Checklists F3SG R User s Manual Checklists...