A Appendices
A - 32
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
•
Set the threshold for differential output of the unit number specified by the index.
•
This object sets the timer function of the Sensor with the unit number that is specified by the index.
•
This object sets the timer value 1 of the Sensor with the unit number that is specified by the index.
•
Timer value 1 is used for the ON delay or the one-shot timer.
•
The setting units for the FA
□
0, LA0, SA0, TA0, MA0, FAH0, EA0, AA
□
0, VA
□
0, VD
□
0 are 1 ms, and
the setting range is 0x0001 (1) - 0x270F (9999).
For the CA0, the settings are selected in increments of 1 (units of 0.1 ms) from 0.1 ms to 0.5 ms, in
increments of 5 (units of 0.5 ms) from 0.5 ms to 5 ms, and in increments of 10 (units of 1ms) from 5
ms to 9999 ms.
The setting range is 0x00000001Hex (1) - 0x00018696 (99990).
0
×
400D + (N-1)
×
80 hex No_01 ... 30 Diffinition Function Response Time
Subindex 0: Number of Entries
Range: 02 hex
Unit: ---
Default: 02 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Diffinition Function Response Time IN1
Range: 0000 to FFFF hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Subindex 2: No_01 ... 30 Diffinition Function Response Time IN2
Range: 0000 to FFFF hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Data
Setting
0001 hex
Response Time 250
μ
S
0002 hex
Response Time 500
μ
S
0003 hex
Response Time 1 mS
0004 hex
Response Time 10 mS
0005 hex
Response Time 100 mS
0
×
400E + (N-1)
×
80 hex No_01 ... 30 Timer Function
Subindex 0: Number of Entries
Range: 02 hex
Unit: ---
Default: 02 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Timer Function IN1
Range: 0000 to FFFF hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Subindex 2: No_01 ... 30 Timer Function IN2
Range: 0000 to FFFF hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Data
Setting
Compatible models
FA
□
0
LA0
SA0
TA0
CA0
MA0
FAH0
EA
□
0 AA
□
0 VA
□
0 VD
□
0
0000 hex
Timer Function OFF
√
√
√
√
√
√
√
√
√
√
√
0001 hex
OFFD (OFF delay)
√
√
√
√
√
√
√
√
√
√
√
0002 hex
ON-D (ON delay)
√
√
√
√
√
√
√
√
√
√
√
0003 hex
SHOT (one-shot)
√
√
√
√
√
√
√
√
√
√
√
0004 hex
ONOFF (ON delay+OFF
delay)
√
√
√
√
√
√
√
√
-
-
-
0005
-00FF hex
Not used.
-
-
-
-
-
-
-
-
-
-
-
400F + (N-1)
×
80 hex
No_01 ... 30 Timer Value 1
Subindex 0: Number of Entries
Range: 02 hex
Unit: ---
Default: 02 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Timer Value 1 IN1
Range: 00000001 hex to 00018696 hex
Unit: ---
Default: --- hex
Attribute: A
Size: 4 bytes (U32)
Access: RW
PDO map: Not possible
Subindex 2: No_01 ... 30 Timer Value 1 IN2
Range: 00000001 hex to 00018696 hex
Unit: ---
Default: --- hex
Attribute: A
Size: 4 bytes (U32)
Access: RW
PDO map: Not possible