7 - 5
7 Function Specifications
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
7-2
Fu
nctio
n
s o
f E3N
W
-ECT
7
7-2
-1 Input
Filter
7-2
Functions of E3NW-ECT
Digital I/O Slave Units have the following convenient functions, in addition to the I/O signal processing.
Purpose
This function prevents data changes and unstable data, which may be caused by fluctuation of input
data and unstable contact state due to chattering and noise. This function is available in Free Run
Mode.
Details of functions
This function reads inputs (ON/OFF) within a certain set time and turn ON the inputs if they are all
same (all ON or all OFF)
,
and turn them OFF if not.
Note that this function works for all inputs of Slave Units and Expansion Units at the same time.
When the input shifts from OFF to ON (or ON to OFF), it is read 4 times from that point at an interval
of 1/4 of the set time. When all read results are ON (or OFF), the input is turned ON (or OFF).
The input filter is set through SDO communications.
The applicable index is 3002 hex.
Refer to the applicable index (Input Filter in Free-Run Mode) in "A-1 Object Dictionary" on page A-2 for
the set values.
7-2-1
Input Filter
Overview of functions
Setting method
1
2
3
4
ON
ON
ON
OFF
OFF OFF
ON
OFF
Data set to be input
Input data is OFF because all data
is not ON during 4 readings.
ON
OFF
OFF
ON
1
2
3
4
ON ON ON ON
Data set to be input
ON delay time
Input data is ON because all data
is ON during 4 readings.